| Notes |
| Date |
Text |
| 2011-04-13 11:14:06 | 1601 BELVEDERE ROAD | | | PERMIT NUMBER 11040079 | | | | | | | | | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION | | | ACTIVITIES TO COMPLY WITH NFPA 241. | | | | | | 2. EXIT ACCESS AND EXITS ARE TO REMAIN CLEAR AND | | | UNOBSTRUCTED. | | | | | | 3. TRASH AND DEBRIS SHALL BE REMOVED DAILY. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE | | | ALARM AND FIRE SPRINKLER SYSTEM RENOVATIONS. | | | | | | 5. ANY EXISTING SMOKE ALARMS THAT ARE TO REMAIN ARE TO | | | BE CHECKED FOR PROPER OPERATION. | | | | | | 6. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRICAL CODE. | | | | | | 7. NO ILLUMINATED EXIT SIGNS OR EMERGENCY LIGHTS | | | DISPLAYED. IT IS ASSUMED THAT SUFFICIENT QUANTITY OF | | | FIXTURES EXIST AND THAT THEY ARE IN GOOD WORKING ORDER. | | | | | | 8. SPRINKLER HEADS ARE TO BE RELOCATED AND NOT CAPPED | | | ABOVE THE CEILING AS DESCRIBED IN THE DRAWINGS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|