Plan Review Notes
Plan Review Notes For Permit 11040079
Permit Number 11040079
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-13 08:33:26BUILDING PLAN REVIEW
 PERMIT: 11040079
 ADD: 1601 BELVEDERE RD
 CONT: TO BE DETERMINED
 TEL: (561)###-####
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE TO OWNER OF A CODE VIOLATION THAT EXIST IN YOUR
 BUILDING. THE ELEVATOR LOBBY IS MISSING SEPERATION AS
 REQUIRED IN THE 2007/09 FBC-B
 SECTION 707.14.1 ELEVATOR LOBBY OR 1 OF THE 6
 EXCEPTIONS. CURRENTLY WE ARE PUTTING YOU ON NOTICE OF
 THIS VIOLATION.
  
 IN THE 2007/09 EXISTING BUILDING CODE SECTION 703.2.2
 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. THE
 WORK WHICH WILL BE COVERED UNDER THIS PERMIT DOES NOT
 MEET THIS REQUIREMENT THUS NOT REQUIRING THE ELEVATOR
 LOBBIES TO BE INSTALLED AT THIS TIME.
  
 ACTION :BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A2.2, A2.3 PLANS INDICATE ALL HOLES FEFT IN
 THE CONCRETE SLAB AFTER PIPE REMOVAL TO BE FIRE RATED-
 ANYTHING OVER 2 INCHES IN DIAMETER TO BE SEALED WITH
 CONCRETE. PLEASE REVIEW FBC-B 712.4.1 FIRE-RESISTANCE
 RATED ASSEMBLIES. PENETRATIONS OF THE FIRE-RESISTANCE
 RATED FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH
 SECTIONS 712.4.1.1 THROUGH 712.4.1.4. PLEASE PROVIDE
 DOCUMENTATION FOR COMPLIANCE PROVIDE CUT SHEET FOR
 PRODUCTS TO BE INSTALLED.
  
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]