2011-04-07 15:30:161400 NORTHPOINT PARKWAY SUITE #20
 PERMIT #11040022
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS***** DRAWINGS WILL BE
 STAMPED, INITIALED, AND DATED BY THE FIRE DEPARTMENT
 AFTER ALL BUILDING DEPARTMENT PLAN REVIEW COMMENTS HAVE
 BEEN SATISFIED.
  
 DOORS SHALL OPEN WITH NOT MORE THAN ONE RELEASING
 MECHANISM.
  
 THUMB TURN LOCKS SHALL VISIBLY INDICATE LOCKED/UNLOCKED
 STATUS.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4 INCHES IN HEIGHT AND HALF INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE NFPA
 101.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS ACCOMPANIED BY
 EXIT SIGNAGE.
  
 INDICATE WHAT MATERIALS WILL BE STORED IN STORAGE ROOM,
 HOW MATERIALS WILL BE STORED, AND STORAGE HEIGHT.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  