| Plan Review Notes For Permit 11040022 |
| Permit Number |
11040022 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-05 12:40:45 | | | | | | | PROVISO: | | | | | | PROVIDE A SINGLE LINE ELECTRIC SERVICE PLAN SHOWING | | | EXISTING AND NEW PANEL BOARDS WITH FEEDERS AND CONDUIT | | | SIZES. NEC 230.2 | | | SUMMARIZE THE LOAD CALCULATION TO VERIFY EXISTING | | | CAPACITY. NEC 220 | | | PROVIDE A SCALE DRAWING OF THE ELECTRICAL ROOM LAYOUT | | | TO ILLUSTRATE THERE ARE ADEQUATE SAFETY CLEARANCES FOR | | | THE EQUIPMENT. NEC 110.26 | | | SECONDARY PROTECTION IS REQUIRED ON THE TRANSFORMERS | | | FEEDING PANELS A, B, AND C. NEC 450.3, TABLE 450.3(B), | | | 240.21 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | | | | SEPARATE PERMITS ARE REQUIRED FOR THE LOW VOLTAGE | | | DATA/PHONE AND FIRE ALARM SYSTEM. | | | | | | | | | ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718 | | | |
|