Plan Review Notes
Plan Review Notes For Permit 11040022
Permit Number 11040022
Review Stop E
Sequence Number 1
Notes
Date Text
2011-04-05 12:40:45 
  
 PROVISO:
  
 PROVIDE A SINGLE LINE ELECTRIC SERVICE PLAN SHOWING
 EXISTING AND NEW PANEL BOARDS WITH FEEDERS AND CONDUIT
 SIZES. NEC 230.2
 SUMMARIZE THE LOAD CALCULATION TO VERIFY EXISTING
 CAPACITY. NEC 220
 PROVIDE A SCALE DRAWING OF THE ELECTRICAL ROOM LAYOUT
 TO ILLUSTRATE THERE ARE ADEQUATE SAFETY CLEARANCES FOR
 THE EQUIPMENT. NEC 110.26
 SECONDARY PROTECTION IS REQUIRED ON THE TRANSFORMERS
 FEEDING PANELS A, B, AND C. NEC 450.3, TABLE 450.3(B),
 240.21
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
  
 SEPARATE PERMITS ARE REQUIRED FOR THE LOW VOLTAGE
 DATA/PHONE AND FIRE ALARM SYSTEM.
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  