| Plan Review Notes For Permit 11030778 |
| Permit Number |
11030778 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-15 11:35:35 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS. SPECIFY ALL | | | DUCT SIZES, ALL OUTLET SIZES AND CFMS PER OUTLET. SHOW | | | THE LOCATIONS AND SIZES OF ALL SUPPLIES, RETURNS, | | | TRANSFER DUCTS, TRANSFER GRILLS, ETC. SPECIFY THE | | | LOCATIONS OF AIR HANDLERS AND CONDENSING UNITS. SPECIFY | | | THE MODEL NUMBERS, AND SPECIFICATIONS FOR THE | | | HEATING/COOLING EQUIPMENT ON THE PLANS. | | | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS. | | | | | | 3) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|