| Notes |
| Date |
Text |
| 2011-05-04 13:52:53 | ***PROVISO*** | | | | | | 1. PER ARCHITECT, 2 HR OCCUPANCY SEPARATION WALL IS | | | EXISTING. PROVIDE SIGNED SEALED LETTER TO INSPECTOR. | | | | | | 2. APPLY FOR CHANGE OF OCCUPANCY FOR ADJACENT TENANT | | | (A3, GYM). | | | | | | 3. REVISION REQUIRED FOR FIRE RATED DOORS (SUBMIT | | | PRODUCT APPROVAL) | | | |
|