| Plan Review Notes For Permit 11030743 |
| Permit Number |
11030743 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-04-29 11:15:03 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE SEE FBC EXISTING BUILDING, 804.2.2, LEVEL 3 | | | ALTERATION REQUIRES COMPLIANCE WITH FBC 907.2.2, | | | AUTOMATIC FIRE DETECTION SYSTEM REQUIRED FOR BUSINESS | | | OCCUPANCY. | | | | | | |
|