| 2011-04-04 13:39:08 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. THE WATER CLOSET IN MENS ROOM #107 WILL REQUIRE A | | | VENT 901.2.1 | | | | | | 2. THE ISOMETRIC DRAWING SHOWS THE TRAPS FOR | | | LAVITORIES, SINKS, URINAL, AND EWC APPEAR TO BE | | | UNDERGROUND 1002.1 | | | | | | 3. THE WATER CLOSETS AND URINAL ARE CONNECTED TO THE | | | HOT WATER SYSTEM ON THE ISO. | | | | | | 4. THE 2 LAVITORIES IN WOMENS ROOM #106 HAVE THE HOT | | | WATER ON THE RIGHT SIDE. | | | | | | 5. THE WATER SUPPLY TO THE WATER COOLER IS NOT SHOWN. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|