| Plan Review Notes For Permit 11030727 |
| Permit Number |
11030727 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-04-11 10:32:32 | RESIDENTIAL (R30 REROOF SECOND CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS TO MATCH | | | INFORMATION ON PAGE 17 OF NOA 09-0820.09 SUBMITTED.: | | | A) NAIL SPACING OF SIDE LAP IS NOT 8". SEE NOA. | | | B) NAIL SPACING OF CENTER ROWS IS NOT 8". SEE NOA. | | | C) APPROVED ASSEMBLY DESIGN PRESSURES IS NOT 60 PSF. | | | SEE NOA. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|