| Plan Review Notes For Permit 11030727 |
| Permit Number |
11030727 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-30 13:35:38 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- FLAT ROOF NOA 07-0730.03 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. NEED CURRENT NOA. VISIT THE MIAMI-DADE | | | WEBSITE AND DOWNLOAD CURRENT NOA. | | | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM | | | CURRENT NOA IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 3- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | IF NOA REQUIRES CALCULATIONS TO BE SIGNED AND SEALED, | | | THEM PROVIDE SIGNED AND SEALED CALCULATIONS. | | | | | | ***NOTE; PERSON DOING THE RAS 117 CALCULATIONS TO TAKE | | | INTO CONSIDERATION THAT ACCORDING TO SEC. R301.2.1.4.3 | | | THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | | | 4- SPECIFY HOW MUCH ROOF SQUARE FOOTAGE IS GOING TO BE | | | RE-ROOFED TO VERIFY COMPLIANCE WITH SEC. 108.3 CITY | | | AMENDMENTS TO FBC. | | | ALSO, SPECIFY THE BUILDING MEAN ROOF HEIGHT. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|