| 2011-04-05 10:01:35 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE FLORIDA STATE PRODUCT APPROVAL IS NOT CURRENT, |
| | R2 (REVISION #2) IS THE CURRENT PRODUCT APPROVAL |
| | VERSION. SEE WWW.FLORIDABUILDING.ORG. IT IS NOT CLEAR |
| | HOW THIS AFFECTS THE PROJECT. A REVIEW HAS BEEN |
| | PERFORMED USING THE DOCUMENTS SUBMITTED BUT WHEN |
| | RESUBMITTING PLEASE REVIEW CURRENT DOCUMENTS FOR |
| | COMPLIANCE. |
| | |
| | 2. CONNECTION TYPE A REQUIRES A CONCRETE SUBSTRATE. |
| | MOST PROJECTS HAVE A CONCRETE SUBSTRATE AT THE TOP, |
| | BLOCK SUBSTRATE AT THE BOTTOM (ALTHOUGH THIS MAY NOT BE |
| | THE CASE DEPENDING ON INSTALLATION METHOD). EITHER |
| | REVISE THE SHUTTER MOUNTING CONNECTION TYPE OR REVISE |
| | THE SUBSTRATE. |
| | |
| | 3. A 2" EDGE DISTANCE FOR TAPCONS REQUIRE A .35 FACTOR, |
| | SEE SHEET 14. FOR INSTANCE, IF ANCHOR SPACING PER THE |
| | CHART IS 10" FOR A 3 1/2" EDGE DISTANCE, 3.5" WOULD BE |
| | REQUIRED FOR 2" EDGE DISTANCE (10" X .35 FACTOR). |
| | |
| | 4. DESIGN PRESSURES TO MEET MINIMUM REQUIREMENTS OF FBC |
| | R301. THE DESIGN PRESSURE PROGRAM PRODUCED DESIGN |
| | PRESSURES WHICH APPEAR TO COMPLY WITH THE CODE |
| | REQUIREMENTS, BUT THESE NUMBERS WERE NOT USED PROPERLY |
| | IN THE INSTALLATION SCHEDULE. FOR INSTANCE, SEE OPENING |
| | 6. THE PROGRAM GAVE DP OF 48.88/-53, BUT THE |
| | INSTALLATION SCHEDULE SPECIFIED 38/-40 (WHICH IS THE |
| | OPENING SIZE). OTHER OPENINGS WERE ROUNDED DOWN TO THE |
| | NEAREST WHOLE NUMBER, FOR INSTANCE OPENING 1 REQUIRED |
| | PRESSURES OF +46.96/-61.49 BUT WAS ROUNDED DOWN TO |
| | 49/-61. IF ROUNDING IS USED, PLEASE ROUND TO THE MORE |
| | CONSERVATIVE WHOLE NUMBER, WHICH WOULD BE +47/-62. |
| | |
| | 5. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| | |
| | ***PLEASE BE ADVISED THAT IN THE FUTURE PERMITS MAY BE |
| | ISSUED WITH PROVISO THAT DOCUMENTS REQUIRED TO |
| | DEMONSTRATE CODE COMPLIANCE BUT NOT PROVIDED AT TIME OF |
| | SUBMITTAL MAY BE ISSUED WITH PROVISO THAT THE REQUIRED |
| | DOCUMENTS BE SUBMITTED AS A REVISION. *** |
| | |