| Plan Review Notes For Permit 11030663 |
| Permit Number |
11030663 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-28 09:11:53 | | | | ****REVISION REQUIRED**** | | | | | | 1. AT 135' THE EXISTING 2" DROP ON THE EAST SIDE WITH | | | TOTAL OF 1,200 K BTU WOULD REQUIRE 2 1/2" PIPE. | | | | | | 2. THE TOTAL BTU OF 1733 K AT 135' WOULD REQUIRE 3" | | | PIPE, BUT THE ISOMETRIC SHOWS 2 1/2" PIPE AFTER THE | | | EMERGENCY VALVE. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|