 ****REVISION REQUIRED****
  
 1. AT 135' THE EXISTING 2" DROP ON THE EAST SIDE WITH
 TOTAL OF 1,200 K BTU WOULD REQUIRE 2 1/2" PIPE.
  
 2. THE TOTAL BTU OF 1733 K AT 135' WOULD REQUIRE 3"
 PIPE, BUT THE ISOMETRIC SHOWS 2 1/2" PIPE AFTER THE
 EMERGENCY VALVE.
  