| Plan Review Notes For Permit 11030659 |
| Permit Number |
11030659 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-04 16:03:14 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPONENTS AND CLADDING INSTALLED IN THE BUILDING | | | ENVELOPE REQUIRE FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL (OR MIAMIDADE NOA). THIS MAY BE AVAILABLE AT | | | WWW.FLORIDABUILDING.ORG. IF A FLORIDA STATE PRODUCT | | | APPROVAL IS SUBMITTED (RATHER THAN A MIAMIDADE NOA), | | | PROVIDE THE COVER SHEET, EVALUATION REPORT, AND | | | INSTALLATION INSTRUCTIONS. | | | | | | 2. THE DOCUMENTS SUBMITTED INCLUDED DOCUMENTS FOR SOLAR | | | STAR ROOF MOUNT VENT AND FOR SOLATUBE SKYLIGHT. A NEW | | | SKYLIGHT INSTALLATION IS NOT WITHIN THE SCOPE OF A | | | ROOFING CONTRACTOR LICENSE. | | | | | | 3. THE DOCUMENTS SUBMITTED STATE THAT THE PRODUCTS ARE | | | FLORIDA BUILDING CODE APPROVED UP TO 120 MPH WINDS. THE | | | CITY OF WEST PALM BEACH LIES ENTIRELY IN THE 140MPH | | | WIND ZONE. | | | | | | 4. PROVIDE A ROOF PLAN WHICH SHOWS ROOF DIMENSIONS, | | | PROPOSED LOCATION OF PROPOSED IMPROVEMENT, INCLUDING | | | DISTANCE TO EDGE OF ROOF FBC R301. | | | | | | 5. PROVIDE BUILIDNG HEIGHT. DESIGN PRESSURES CANNOT BE | | | DETERMINED BASED ON INFORMATION PROVIDED. | | | | | | | | | | | | | | | |
|