| Plan Review Notes For Permit 11030620 |
| Permit Number |
11030620 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-04-05 16:54:29 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT | | | COVER THE 73-1/2" X 80 " OR THE 111" X 50 " HORIZONTAL | | | SLIDING WINDOWS SPECIFIED ON THE FLOOR PLAN. SUBMIT | | | PRODUCT APPROVALS FOR THESE SIZE WINDOWS. THE LOCAL | | | PRODUCT APPROVAL WAS DENIED. | | | | | | 2) THE STRUCTURE IS LOCATED IN 140 MPH WIND SPEED AND | | | EXPOSURE CATEGORY C. HIGHLITE THE WINDOW SIZES AND | | | GLASS TYPE IN THE TABLES IN THE PRODUCT APPROVALS. MAKE | | | SURE THAT THE POSITIVE AND NEGATIVE PRESSURES FROM THE | | | TABLES ARE HIGHER THAN THE REQUIRED DESIGN LOADS FOR | | | COMPONENTS AND CLADDING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|