2011-03-31 09:59:122007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE FLOOR PLAN THAT WAS SUBMITTED PROVIDES THE
 OPENING SIZES BUT DOES NOT SPECIFY THE TYPE OF WINDOW
 AT EACH LOCATION. PLEASE CORRECT.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT
 COVER THE 73-1/2" X 80 " OR THE 111" X 50 " WINDOWS
 SPECIFIED ON THE FLOOR PLAN. SUBMIT PRODUCT APPROVALS
 FOR THESE SIZE WINDOWS. IF THESE ARE WINDOWS THAT ARE
 MULLED TOGETHER, LIST THE INDIVIDUAL WINDOW SIZES AND
 SPECIFY THE NUMBER OF THEM THAT ARE MULLED TOGETHER AND
 SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS.
  
 3) THE STRUCTURE IS LOCATED IN 140 MPH WIND SPEED AND
 EXPOSURE CATEGORY C. HIGHLITE THE WINDOW SIZES AND
 GLASS TYPE IN THE TABLES IN THE PRODUCT APPROVALS. MAKE
 SURE THAT THE POSITIVE AND NEGATIVE PRESSURES FROM THE
 TABLES ARE HIGHER THAN THE REQUIRED DESIGN LOADS FOR
 COMPONENTS AND CLADDING.
  
 4) SPECIFY THE ROOM TYPES IN WHICH THE WINDOWS ARE
 LOCATED ON THE FLOOR PLAN.
  