| Plan Review Notes For Permit 11030620 |
| Permit Number |
11030620 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-31 09:59:12 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE FLOOR PLAN THAT WAS SUBMITTED PROVIDES THE | | | OPENING SIZES BUT DOES NOT SPECIFY THE TYPE OF WINDOW | | | AT EACH LOCATION. PLEASE CORRECT. | | | | | | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT | | | COVER THE 73-1/2" X 80 " OR THE 111" X 50 " WINDOWS | | | SPECIFIED ON THE FLOOR PLAN. SUBMIT PRODUCT APPROVALS | | | FOR THESE SIZE WINDOWS. IF THESE ARE WINDOWS THAT ARE | | | MULLED TOGETHER, LIST THE INDIVIDUAL WINDOW SIZES AND | | | SPECIFY THE NUMBER OF THEM THAT ARE MULLED TOGETHER AND | | | SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS. | | | | | | 3) THE STRUCTURE IS LOCATED IN 140 MPH WIND SPEED AND | | | EXPOSURE CATEGORY C. HIGHLITE THE WINDOW SIZES AND | | | GLASS TYPE IN THE TABLES IN THE PRODUCT APPROVALS. MAKE | | | SURE THAT THE POSITIVE AND NEGATIVE PRESSURES FROM THE | | | TABLES ARE HIGHER THAN THE REQUIRED DESIGN LOADS FOR | | | COMPONENTS AND CLADDING. | | | | | | 4) SPECIFY THE ROOM TYPES IN WHICH THE WINDOWS ARE | | | LOCATED ON THE FLOOR PLAN. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|