2011-03-30 11:17:402007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1.) PLEASE PROVIDE A DRAWING OF THE
 FOOTPRINT OF THE HOUSE INDICATING
 THE LOCATIONS AND SIZES OF THE WINDOWS
 WHICH ARE TO BE REPLACED.
  
 2.) PLEASE INDICATE ON THE HOUSE
 FOOTPRINT DRAWING ALL BEDROOM WINDOWS. THE BEDROOM
 WINDOWS ARE REQUIRED BY THE CODE AS EMERGENCY ESCAPE
 AND RESCUE OPENINGS. THE CODE ALLOWS ONLY A 5 PERCENT
 REDUCTION TO THE EXISTING CLEAR OPENING DIMENSIONS. FBC
 EXISTING BUILDING CODE SEC. 604
  
 3) THE PROPOSED WINDOWS ARE NOT IMPACT RATED AND ARE
 REQUIRED TO HAVE IMPACT PROTECTION. IF YOU ARE
 REPLACING 25 PERCENT OR MORE OF THE TOTAL GLAZED AREA
 IN THE BUILDING, IMPACT PROTECTION IS REQUIRED PER FBC
 EXISTING BUILDING CODE SEC. 606.4. SUBMIT 2 SETS OF
 PRODUCT APPROVALS FOR THE STORM PANELS, ALONG WITH A
 KEY PLAN AND INSTALLATION SCHEDULE. AN INSTALLATION
 SCHEDULE FORM IS AVAILABLE ON THE CONSTRUCTION SERVICES
 WEBSITE.
  
 4) THE WINDOW PRODUCT APPROVAL HAS TWO TYPES OF WINDOWS
 IN IT. PLEASE SPECIFY THE WINDOW TYPE THAT WILL BE
 INSTALLED AT EACH LOCATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]