| Plan Review Notes For Permit 11030563 |
| Permit Number |
11030563 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-28 12:40:57 | PLANS DENIED | | | REFER TO SECTION 601.4 2007 FBC (M) BALANCED RETURN AIR | | | . | | | REFER TO SECTION 606.2.1 2007 FBC (M) SUPPLY SYSTEM. IF | | | DUCT DETECTORS ARE NOT INSTALLED PROVIDE A LETTER FROM | | | THE MANUFACTURE'S ENGINEER SAYING THAT IN NO SHAPE OR | | | FORM WILL THE AIR HANDLER PRODUCE MORE THAN 2000 CFM. | | | REFER TO SECTION 606.3 INSTALLATION 2007 FBC (M) | | | REFER TO SECTION 602.2.1 MATERIALS EXPOSED WITH IN | | | PLENUMS, MATERIALS WITH IN PLENUMS SHALL BE | | | NONCOMBUSTIBLE. DOOR SCHEDULE SHOWS A WOOD DOOR. | | | REFER TO SECTION 306 2007 FBC (M) ACCESS TO EQUIPMENT | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|