2011-04-05 09:03:31PLEASE SUBMIT AN ELECTRICAL FLOOR PLAN SHOWING THE NEW
 RECEPTACLES WITH AFCI PROTECTION, GFCI PROTECTION AND
 TAMPER RESISTANT AS APPROPRIATE FOR THE INTENDED USE.
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A
 SWITCHED RECEPTACLE OR LIGHT AND A SWITCHED OUTSIDE
 LIGHT. AT LEAST ONE GFCI PROTECTED RECEPTACLE IS
 REQUIRED OUTSIDE.
  
 PROVIDE A ONE LINE ELECTRICAL SERVICE RISER DIAGRAM
 SHOWING THE SIZE OF THE EXISTING ELECTRIC SERVICE. SHOW
 LOCATION OF ELECTRICAL PANEL.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES OR A FIRE PLACE A CARBON MONOXIDE
 DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED
 FOR SLEEPING.
  
 2008 NATIONAL ELECTRIC CODE REFERENCES:
 SECTIONS 210.8, 210.12, 210.52, 210.70, 406.11
  
 2007 FLORIDA RESIDENTIAL BUILDING CODE REFERENCE:
 SECTION R313
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  
  