| Plan Review Notes For Permit 11030546 |
| Permit Number |
11030546 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-05 09:03:31 | PLEASE SUBMIT AN ELECTRICAL FLOOR PLAN SHOWING THE NEW | | | RECEPTACLES WITH AFCI PROTECTION, GFCI PROTECTION AND | | | TAMPER RESISTANT AS APPROPRIATE FOR THE INTENDED USE. | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A | | | SWITCHED RECEPTACLE OR LIGHT AND A SWITCHED OUTSIDE | | | LIGHT. AT LEAST ONE GFCI PROTECTED RECEPTACLE IS | | | REQUIRED OUTSIDE. | | | | | | PROVIDE A ONE LINE ELECTRICAL SERVICE RISER DIAGRAM | | | SHOWING THE SIZE OF THE EXISTING ELECTRIC SERVICE. SHOW | | | LOCATION OF ELECTRICAL PANEL. | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES OR A FIRE PLACE A CARBON MONOXIDE | | | DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED | | | FOR SLEEPING. | | | | | | 2008 NATIONAL ELECTRIC CODE REFERENCES: | | | SECTIONS 210.8, 210.12, 210.52, 210.70, 406.11 | | | | | | 2007 FLORIDA RESIDENTIAL BUILDING CODE REFERENCE: | | | SECTION R313 | | | | | | ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718 | | | | | | | | | |
|