| Plan Review Notes For Permit 11030546 |
| Permit Number |
11030546 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-12 11:11:37 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) PROVIDE THE DESIGN CRITERIA ON THE PLANS. THE | | | WIND-SPEED IS 140 MPH AND THE EXPOSURE CATEGORY IS C. | | | FBC R301 | | | | | | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE | | | WINDOWS AND DOORS ON THE PLANS. FBC R301.2.1 | | | | | | 3) SPECIFY THE SQUARE FOOTAGE OF THE ENCLOSED PORCH | | | ADDITION ON THE PLANS. | | | | | | 4) THE FINISH FLOOR ELEVATION IS REQUIRED TO BE A | | | MINIMUM OF 4 INCHES ABOVE FINISH GRADE FOR MASONRY | | | WALLS. PLEASE SPECIFY ON THE PLANS. FBC R 404.1.6 | | | | | | 5) THE SOIL IS TO BE COMPACTED AND TREATED FOR TERMITES | | | AT THE NEW FOOTERS. FBC R401.2 AND R320 | | | | | | 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | IMPACT WINDOWS THAT WILL BE INSTALLED. SPECIFY THE | | | WINDOW TYPES AND SIZES ON THE PLANS. DCA RULE 9B-72 | | | | | | 7) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED IS | | | REQUIRED TO BE SIGNED BY THE OWNER/AGENT. | | | | | | 8) THE ENERGY FORM THAT WAS SUBMITTED REQUIRES A | | | MINIMUM INSULATION VALUE OF R-6 FOR THE EXTERIOR MASS | | | WALLS. THE PLANS SPECIFY R-5 INSULATION. PLEASE REVISE | | | PLANS. | | | | | | 9) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM | | | BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|