| Date |
Text |
| 2011-08-08 13:22:54 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS: |
| | |
| | 1- PROPERTY IS LOCATED ON FLOOD ZONE A9 (ELEV. 13). |
| | CITY ORDINANCE REQUIRES FINISH FLOOR ELEVATION TO BE AT |
| | LEAST 6" ABOVE THE BASE FLOOD ELEVATION. CITY ORDINANCE |
| | ARTICLE XVII SEC. 94-546(B)(1). |
| | |
| | A) REVISED FLOOR PLANS SHOW PROPOSED FINISH FLOOR |
| | ELEVATION TO BE 13.09'. NEED TO HAVE MIN. 6" ABOVE THE |
| | BASE FLOOD ELEVATION. SEE CITY ORDINANCE ABOVE. FINISH |
| | FLOOR ELEVATION NEED TO BE MIN. 13'-6". REVISE PLANS AS |
| | REQUIRED. THIS ELEVATION IS REQUIRED FOR ALL EQUIPMENT |
| | (EX: A/C EQUIPMENT). REVISE PLANS AS REQUIRED. AND, |
| | SPECIFY NEW CEILING HEIGHT TO VERIFY COMPLIANCE WITH |
| | SEC. R305. |
| | |
| | B) ENGINEER TO CERTIFY ON PLANS THAT PLANS ARE DESIGNED |
| | TO ALLOW FOR THE ENTRY AND EXIT OF FLOOD WATERS AS |
| | REQUIRED BY CITY ORDINANCE SEC. 94-546(E). PROVIDE |
| | COMPLETE DETAILS/SPECIFICATIONS. SHOW FLOOD VENTS SIZES |
| | AND LOCATION. |
| | |
| | ***NOTE: THERE ARE COMBINATION FLOOD/VENTILATION VENTS |
| | THAT CAN BE USED. COORDINATE WITH ITEM #3 BELOW. |
| | |
| | 2- REVISE SECTION DETAIL S-2 ON SHEET A-2.0. NEED TO |
| | SPECIFY JOIST HANGERS. FLOOR NEEDS TO BE RAISED TO |
| | COMPLY WITH ITEM #1 ABOVE. CITY ORDINANCE SEC. |
| | 94-546(B)(1). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE WALL FLOOD VENTS. |
| | *** FOR YOUR INFORMATION: THERE ARE PRODUCT APPROVALS |
| | FOR COMBINATION FLOOD VENT AND CRAWL SPACE VENTILATION. |
| | COORDINATE WITH ITEM #1 ABOVE. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 5- STORM SHUTTERS. REVISE INSTALLATION SCHEDULE. REVISE |
| | SHUTTER PANEL LENGTH FOR OPENING #4. TABLE 2 ON PAGE 6 |
| | OF 6 OF SHUTTERS DRAWINGS REQUIRE MIN. LENGTH TO BE |
| | 52". REVISE AS REQUIRED. |
| | |
| | 6- ENERGY CALCULATIONS SUBMITTED: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM. |
| | |
| | B) CLARIFY ITEM #2 AND #3. PLANS SHOWS TWO INDEPENDENT |
| | DWELLING UNITS. |
| | |
| | 7- PLEASE PROVIDE WRITTEN RESPONSE TO EACH ITEM TO |
| | EXPEDITE THE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |