Plan Review Notes
Plan Review Notes For Permit 11030525
Permit Number 11030525
Review Stop B
Sequence Number 2
Notes
Date Text
2011-08-08 13:22:54RESIDENTIAL (R3) ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS:
  
 1- PROPERTY IS LOCATED ON FLOOD ZONE A9 (ELEV. 13).
 CITY ORDINANCE REQUIRES FINISH FLOOR ELEVATION TO BE AT
 LEAST 6" ABOVE THE BASE FLOOD ELEVATION. CITY ORDINANCE
 ARTICLE XVII SEC. 94-546(B)(1).
  
 A) REVISED FLOOR PLANS SHOW PROPOSED FINISH FLOOR
 ELEVATION TO BE 13.09'. NEED TO HAVE MIN. 6" ABOVE THE
 BASE FLOOD ELEVATION. SEE CITY ORDINANCE ABOVE. FINISH
 FLOOR ELEVATION NEED TO BE MIN. 13'-6". REVISE PLANS AS
 REQUIRED. THIS ELEVATION IS REQUIRED FOR ALL EQUIPMENT
 (EX: A/C EQUIPMENT). REVISE PLANS AS REQUIRED. AND,
 SPECIFY NEW CEILING HEIGHT TO VERIFY COMPLIANCE WITH
 SEC. R305.
  
 B) ENGINEER TO CERTIFY ON PLANS THAT PLANS ARE DESIGNED
 TO ALLOW FOR THE ENTRY AND EXIT OF FLOOD WATERS AS
 REQUIRED BY CITY ORDINANCE SEC. 94-546(E). PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS. SHOW FLOOD VENTS SIZES
 AND LOCATION.
  
 ***NOTE: THERE ARE COMBINATION FLOOD/VENTILATION VENTS
 THAT CAN BE USED. COORDINATE WITH ITEM #3 BELOW.
  
 2- REVISE SECTION DETAIL S-2 ON SHEET A-2.0. NEED TO
 SPECIFY JOIST HANGERS. FLOOR NEEDS TO BE RAISED TO
 COMPLY WITH ITEM #1 ABOVE. CITY ORDINANCE SEC.
 94-546(B)(1).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE WALL FLOOD VENTS.
 *** FOR YOUR INFORMATION: THERE ARE PRODUCT APPROVALS
 FOR COMBINATION FLOOD VENT AND CRAWL SPACE VENTILATION.
 COORDINATE WITH ITEM #1 ABOVE.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- STORM SHUTTERS. REVISE INSTALLATION SCHEDULE. REVISE
 SHUTTER PANEL LENGTH FOR OPENING #4. TABLE 2 ON PAGE 6
 OF 6 OF SHUTTERS DRAWINGS REQUIRE MIN. LENGTH TO BE
 52". REVISE AS REQUIRED.
  
 6- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM.
  
 B) CLARIFY ITEM #2 AND #3. PLANS SHOWS TWO INDEPENDENT
 DWELLING UNITS.
  
 7- PLEASE PROVIDE WRITTEN RESPONSE TO EACH ITEM TO
 EXPEDITE THE REVIEW PROCESS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved