| Plan Review Notes For Permit 11030499 |
| Permit Number |
11030499 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-04-11 17:01:05 | LINK TO SAMPLE INSTALLATION SCHEDULE: | | | | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | | | 2011-04-07 10:28:36 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE KEY PLAN INCORRECTLY LISTS ASCE 7-98 AND | | | EXPOSURE CATEGORY B. PLEASE CORRECT. | | | | | | 2) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE FOR THE | | | ACCORDION SHUTTERS. SPECIFY THE OPENING PRESSURES, THE | | | MOUNTING METHOD, THE SPANS, GLASS SEPARATION, ANCHOR | | | TYPES, ANCHOR SPACING, ETC. THE FORM IS AVAILABLE ON | | | THE CONSTRUCTION SERVICES WEBSITE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|