Plan Review Notes
Plan Review Notes For Permit 11030499
Permit Number 11030499
Review Stop B
Sequence Number 1
Notes
Date Text
2011-03-30 09:13:092007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE COMPONENT AND CLADDING PRESSURE TABLES THAT WERE
 SUBMITTED ARE NOT ACCEPTABLE. THE BUILDING IS LOCATED
 IN EXPOSURE CATEGORY C NOT B. THE BUILDINGS HAS A MEAN
 ROOF HEIGHT OF WELL ABOVE 60'. THE 2007 FLORIDA
 BUILDING CODE AND ASCE 7-05 ARE THE EDITIONS IN EFFECT
 AT THIS TIME. PLEASE PROVIDE CORRECT ENGINEERING.
  
 2) THE KEY PLAN INCORRECTLY LISTS ASCE 7-98 AND
 EXPOSURE CATEGORY B. PLEASE CORRECT.
  
 3) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE FOR THE
 ACCORDION SHUTTERS. SPECIFY THE OPENING PRESSURES, THE
 MOUNTING METHOD, THE SPANS, GLASS SEPARATION, ANCHOR
 TYPES, ANCHOR SPACING, ETC. THE FORM IS AVAILABLE ON
 THE CONSTRUCTION SERVICES WEBSITE.
  
 4) ACCORDING TO THE MIAMI DADE WEBSITE THE PRODUCT
 APPROVAL FOR THE TROPICAL DEPRESSION SHUTTER INDUSTRIES
 ACCORDION SHUTTERS HAS A CLOSED FILE STATUS. PLEASE
 SUBMIT A CURRENT PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]