| 2011-03-30 09:13:09 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE COMPONENT AND CLADDING PRESSURE TABLES THAT WERE | | | SUBMITTED ARE NOT ACCEPTABLE. THE BUILDING IS LOCATED | | | IN EXPOSURE CATEGORY C NOT B. THE BUILDINGS HAS A MEAN | | | ROOF HEIGHT OF WELL ABOVE 60'. THE 2007 FLORIDA | | | BUILDING CODE AND ASCE 7-05 ARE THE EDITIONS IN EFFECT | | | AT THIS TIME. PLEASE PROVIDE CORRECT ENGINEERING. | | | | | | 2) THE KEY PLAN INCORRECTLY LISTS ASCE 7-98 AND | | | EXPOSURE CATEGORY B. PLEASE CORRECT. | | | | | | 3) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE FOR THE | | | ACCORDION SHUTTERS. SPECIFY THE OPENING PRESSURES, THE | | | MOUNTING METHOD, THE SPANS, GLASS SEPARATION, ANCHOR | | | TYPES, ANCHOR SPACING, ETC. THE FORM IS AVAILABLE ON | | | THE CONSTRUCTION SERVICES WEBSITE. | | | | | | 4) ACCORDING TO THE MIAMI DADE WEBSITE THE PRODUCT | | | APPROVAL FOR THE TROPICAL DEPRESSION SHUTTER INDUSTRIES | | | ACCORDION SHUTTERS HAS A CLOSED FILE STATUS. PLEASE | | | SUBMIT A CURRENT PRODUCT APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|