| 2011-04-14 14:16:14 | 2007 FBC W/2009 REVISIONS |
| | DENIED BY BUILDING |
| | |
| | 1) FBC R 806.1 REQUIRES ENCLOSED RAFTER SPACES FORMED |
| | WHEN CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF |
| | ROOF RAFTERS TO HAVE CROSS VENTILATION OF EACH SEPARATE |
| | SPACE THEREFORE A CONTINUOUS SOFFIT VENT OR OTHER |
| | METHOD WILL BE REQUIRED. SEE SECTION B ON SHEET 5. |
| | |
| | 2) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A |
| | BOND BREAK BETWEEN THE STUCCO AND THE WATER RESISTIVE |
| | BARRIER. |
| | |
| | 3) A FOUNDATION WEEP SCREED IS REQUIRED AT THE BOTTOM |
| | OF ALL FRAMED EXTERIOR STUCCO WALLS IN ACCORDANCE WITH |
| | ASTM C 1063. |
| | |
| | 4) ASTM C 926 REQUIRES THE STUCCO APPLIED OVER METAL |
| | LATH ON VERTICAL WALLS TO BE A MINIMUM OF 7/8 INCH |
| | THICK. SECTION B ON SHEET 5 SPECIFIES 5/8 INCH STUCCO. |
| | PLEASE CORRECT. |
| | |
| | 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ADDITION. |
| | |
| | 6) PLEASE CLARIFY THE COMPONENT AND CLADDING PRESSURES |
| | THAT ARE SPECIFIED ON THE PLANS WERE DETERMINED. THE |
| | STRUCTURE IS LOCATED IN 140 MPH 3 SECOND GUST WIND |
| | SPEED AND EXPOSURE CATEGORY C. PROVIDE THE MEAN ROOF |
| | HEIGHT, WALL ZONE AND EFFECTIVE WIND AREA USED TO |
| | DETERMINE THESE PRESSURES. |
| | |
| | 7) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL WINDOW MULLIONS AND THE STORM PANELS THAT |
| | WILL BE INSTALLED. |
| | |
| | 8) SUBMIT TWO COPIES OF A KEY PLAN AND AN INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. THIS IS THE LINK TO A |
| | SAMPLE OF AN INSTALLATION SCHEDULE ON THE CONSTRUCTION |
| | SERVICES WEB SITE HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION |
| | /PDF/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | FRENCH DOORS WITH SIDELITES ARE NOT THE ONES THAT ARE |
| | SPECIFIED ON THE PLANS. THE PLANS SPECIFY MASONITE |
| | INTERNATIONAL AND THE PRODUCT APPROVALS ARE FOR |
| | THERMA-TRU. THE DESIGN PRESSURES FOR THE THERMA-TRU OUT |
| | SWING GLAZED DOORS WITH SITELITES ARE +47,-47 PSF WHICH |
| | ARE LESS THAN THE REQUIRED COMPONENT AND CLADDING |
| | PRESSURES. PLEASE CORRECT. |
| | |
| | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SINGLE HUNG AND FIXED WINDOWS ARE NOT THE ONES THAT ARE |
| | SPECIFIED ON THE PLANS. PLEASE CORRECT. NOTE: THE |
| | PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 11) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH |
| | COUNTY TO DETERMINE IF IMPACT FEES ARE DUE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |