| Plan Review Notes For Permit 11030458 |
| Permit Number |
11030458 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-17 12:49:46 | ADDITIONAL RECEPTACLES ARE REQUIRED. THEY SHALL BE | | | SPACED SO THAT AT NO POINT ALONG THE FLOOR IN ANY WALL | | | IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC | | | 210.52 (A)(2). | | | ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE | | | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER. | | | NEC 210-12 (B) | | | ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | | 406.11 | | | AN ELECTRICAL PERMIT IS REQUIRED FOR THIS WORK. | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | | | | |
|