| Plan Review Notes For Permit 11030438 |
| Permit Number |
11030438 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-30 09:51:12 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET P-2 & P-3 SHOW A SINK INSIDE THE WET VENT FOR | | | THE WATER CLOSET. PLEASE SHOW THE SINK DOWNSTREAM OF | | | THE WET VENT. | | | 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF | | | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME | | | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR | | | THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF | | | THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE | | | DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|