Plan Review Notes
Plan Review Notes For Permit 11030438
Permit Number 11030438
Review Stop M
Sequence Number 1
Notes
Date Text
2011-04-07 12:55:08REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. IF EXHAUST FIRE DAMPER IS NEW, A FIRE AND SMOKE
 DAMPER IS REQUIRED AT THE EXHAUST SHAFT PENETRATION PER
 FBC-M 607.5.5.
  
 2. FIRE DAMPER AND FIRE/SMOKE DAMPER SYMBOLS ON THIS
 PAGE DO NOT CORRESPOND WITH THOSE USED IN THE SYMBOL
 LEGEND ON PAGE M1. PLEASE CORRECT.
  