| Plan Review Notes For Permit 11030438 |
| Permit Number |
11030438 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-04-04 15:38:41 | 777 SOUTH FLAGLER DRIVE, 12TH FLOOR | | | PERMIT NUMBER 11030438 | | | | | | 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. DUSTPROOF WALLS SHALL NOT BE CONSTRUCTED OF | | | MATERIALS THAT ARE FLAMMABLE OR COMBUSTIBLE. | | | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM SYSTEMS REMODELING. | | | | | | 4. EXISTING HORIZONTAL AND VERTICAL FIRE SEPARATIONS | | | ARE TO BE MAINTAINED. | | | | | | 5. PLEASE PROVIDE FLAMESPREAD DETAILS FOR FABRIC | | | CEILING PANELS DISPLAYED ON SHEET A5.2. | | | | | | 6. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE | | | WITH ANY EXITING. | | | | | | 7. PLEASE PROVIDE FLAMESPREAD DETAILS FOR WOOD VENEER | | | WALL PANELS. | | | | | | 8. THE INSTALLATION OF SOFFITS SHALL NOT INTERFERE WITH | | | THE OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | 9. ALL NEW FIRE DAMPERS ARE TO BE DROP TESTED TO ENSURE | | | PROPER OPERATION. | | | | | | 10. CLOSET AND OFFICE NEAR RECEPTION DESK APPEARS TO BE | | | ABSENT OF FIRE SPRINKLER HEADS ON SHEET FS2. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|