Plan Review Notes
Plan Review Notes For Permit 11030423
Permit Number 11030423
Review Stop P
Sequence Number 1
Notes
Date Text
2011-04-07 12:59:42FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 P101G SHOWS A LAV OUTSIDE OF THE BATHROOM ON THE DEMO
 PLAN.
 P201G NOTE 41 STATES RECONNECT WALL HUNG LAVATORY TO
 EXISTING 1 1/4" WASTE. FROM P101G IT APPEARS THAT THERE
 WOULD NOT BE AN EXISTING WASTE TO CONNECT TO. PLEASE
 SUBMIT AN ISOMETRIC SHOWING SANITARY AND WATER TO NEW
 LAV LOCATION.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR