| 2011-03-24 16:39:21 | 1200 7TH STREET |
| | PERMIT #11030392 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: THIS IS A CHANGE OF OCCUPANCY FROM EXISTING |
| | FAMILY DWELLING TO NEW BUSINESS. |
| | |
| | |
| | EXITING SHALL COMPLY WITH LIFE SAFETY CODE CHAPTER 7 OF |
| | NFPA 101 FLORIDA EDITION 2007. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | PROVIDE EXIT SIGNS AND TACTILE SIGNAGE AT EXIT DOORS |
| | READING EXIT. |
| | |
| | COOKING EQUIPMENT SHALL BE PROTECTED WITH A FIXED FIRE |
| | SUPPRESSION SYSTEM. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |