| Plan Review Notes For Permit 11030378 |
| Permit Number |
11030378 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-17 10:48:10 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SHEET A1, TYPICAL INTERIOR WALL PARTITION, IT IS NOT | | | CLEAR WHAT WILL SUPPORT THE TOP OF THE WALL. SPEC | | | STATES "FASTER (SIC) TO UNDERSIDE OF ROOF" BUT THE | | | GRAPHIC SHOWING SUPPORT HAS BEEN REMOVED. REVISE WALL | | | DETAIL. | | | | | | 2. INSPECTION COMMENTS REQUEST A SOFFIT DETAIL. NO | | | SOFFITS ARE SHOWN ON THE PLAN. PLEASE BE ADVISED THAT | | | THE PLAN SUBMITTED DOES NOT ADDRESS THE INSPECTION | | | COMMENT. | | | | | | 3. SHOW DISTANCE BETWEEN THE SODA MACHINE AND WALL, | | | SODA MACHINE TO EDGE OF THE ACCESSIBLE COUNTER. THE | | | SALES COUNTER IS TO BE LOCATED ON AN ACCESSIBLE ROUTE | | | COMPLYING WITH FBC 11-4.3 PER FBC 11-7.2. | | | |
|