2011-03-11 15:25:10RESIDENTIAL (R3) ROOF REPAIRS, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS
  
 1- PROPOSED REPAIRS ARE NOT ALLOWED BY SEC. 611.1.1 OF
 2007 FBC-EXISTING BUILDING.
  
 2- FLAT ROOF NOA 08-0118.07 SUBMITTED EXPIRED ON
 03/08/11. NEED TO PROVIDE CURRENT NOA.
  
 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED
 BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 4- NEED BUILDING PERMIT TO DO THE HURRICANE STRAPPING.
 CONTRACTOR NEEDS TO HAVE PROPER LICENSE TO DO THE
 STRUCTURAL WORK. ROOFING CONTRACTOR IS NOT ALLOWED TO
 PERFORM THIS JOB. CONTACT PALM BEACH COUNTY LICENSING
 BOARD REGARDING ROOFING CONTRACTOR SCOPE OF WORK.
  
 5- PROVIDE ORIGINAL ENGINEERING LETTER (SIGNED AND
 SEALED AS REQUIRED BY SEC. 472 FLORIDA STATUTES)
 SPECIFYING STRAPS REQUIRED FOR THIS HOUSE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712