| 2011-07-26 09:35:08 | PLANS DENIED | | | PLEASE PROVIDE THE CUBIC FEET OF THE MECHANICAL ROOM ON | | | THE PLANS . | | | PLEASE PROVIDED THE AMOUNT OF REFRIGERANT IN THE | | | CHILLER . | | | PER SECTION 1103.1 FBC (M) 2007 . | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|