2011-03-24 14:47:33FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 FROM THE SCOPE OF WORK ON THESE PLANS IT APPEARS THAT
 THE PRIME CONTRACTOR WOULD BE MECHANICAL.
 A MECHANICAL MASTER PERMIT WITH MECHANICAL DRAWINGS,
 ELECTRICAL SUB- PERMIT, BUILDING SUB- PERMIT, AND
 PLUMBING SUB- PERMIT WILL BE REQUIRED WITH FULL VALUE
 CONCERNING THESE CONTRACTORS.
  
 A SEPERATE WELL PERMIT WILL BE REQUIRED. PALM BEACH
 COUNTY HEALTH DEPT. APPROVAL FOR THE WELL WILL BE
 REQUIRED BEFORE WELL PERMIT ISSUANCE.
  
 A GAS APPLICATION, ISOMETRIC DRAWING WITH ALL REQUIRED
 INFORMATION, AND PERMIT WILL BE REQUIRED.
  
 ****PLUMBING NOTES****
  
 1. WELL WATER HOSE BIBBS SHALL HAVE WARNING SIGNAGE,
 NON-POTABLE WATER
  
 2. CITY CODE 90-33 THE WELL WATER AND DOMESTIC WATER
 SHALL NOT BE COMBINED IN ANY WAY. (AN AIR GAP WHERE
 DOMESTIC WATER ENTERS THE EVAPORATIVE CONDENSER, ETC.
 WOULD BE OK)
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  