| Plan Review Notes For Permit 11030372 |
| Permit Number |
11030372 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-24 14:47:33 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | FROM THE SCOPE OF WORK ON THESE PLANS IT APPEARS THAT | | | THE PRIME CONTRACTOR WOULD BE MECHANICAL. | | | A MECHANICAL MASTER PERMIT WITH MECHANICAL DRAWINGS, | | | ELECTRICAL SUB- PERMIT, BUILDING SUB- PERMIT, AND | | | PLUMBING SUB- PERMIT WILL BE REQUIRED WITH FULL VALUE | | | CONCERNING THESE CONTRACTORS. | | | | | | A SEPERATE WELL PERMIT WILL BE REQUIRED. PALM BEACH | | | COUNTY HEALTH DEPT. APPROVAL FOR THE WELL WILL BE | | | REQUIRED BEFORE WELL PERMIT ISSUANCE. | | | | | | A GAS APPLICATION, ISOMETRIC DRAWING WITH ALL REQUIRED | | | INFORMATION, AND PERMIT WILL BE REQUIRED. | | | | | | ****PLUMBING NOTES**** | | | | | | 1. WELL WATER HOSE BIBBS SHALL HAVE WARNING SIGNAGE, | | | NON-POTABLE WATER | | | | | | 2. CITY CODE 90-33 THE WELL WATER AND DOMESTIC WATER | | | SHALL NOT BE COMBINED IN ANY WAY. (AN AIR GAP WHERE | | | DOMESTIC WATER ENTERS THE EVAPORATIVE CONDENSER, ETC. | | | WOULD BE OK) | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|