| 2011-03-23 11:21:15 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. 1002.1 WASHING MACHINE AND FLOOR DRAIN ARE NOT SHOWN | | | AS BEING TRAPPED. FLOOR DRAIN REQUIRES A TRAP | | | PRIMER.1002.4 | | | | | | 2. FBC 106.3.5.1.3 PLEASE INCLUDE HOT AND COLD WATER | | | DIAGRAM INCLUDING ALSO STEAM PIPEING. | | | | | | 3. PLEASE SHOW THE LOCATION OF THE EXISTING BOTTLED | | | WATER DISPENSER OR ADD THE REQUIRED DRINKING FOUNTAIN | | | PER 403.1 MINIMUM FIXTURES. | | | | | | ****NOTE**** | | | PLEASE SEE NOTE 8 IN BUILDING REVIEW. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | |
|