Plan Review Notes
Plan Review Notes For Permit 11030363
Permit Number 11030363
Review Stop M
Sequence Number 1
Notes
Date Text
2011-03-17 09:02:19PLANS DENIED
  
 1. VENITLATION REQUIRED IN STEAM ROOM AND SHOWER, FBC M
 403. VENTILATION NOT SPECIFIED IN THE SHOWER AND NOT
 SPECIFIED OR SHOWN IN THE STEAM ROOM.
  
 2. VENTILATION NOT SHOWN OR SPECIFIED IN THE W/C ROOMS,
 FBC M 403.
  
 3. PLEASE REVIEW PLAN TO PROVIDE MORE INFORMATION
 REGARDING W/C ROOMS, A SMALL SYMBOL FOR SUPPLY IS SHOWN
 IN ONE BUT NOT IN THE NEW ALTERED W/C. PLEASE SHOW ALL
 EXISTING AND PROPOSED NEW SUPPLY FBC M 403.
  
 4. ELECTRIC PLAN SHOWS TWO WATER HEATERS, SHEET M2
 SHOWS ONE. PLEASE CORRELATE. ARE THEY GAS OR ELECTRIC
 WATER HEATERS? FBC M 1002.
  
 PLAN REVIEW BY HAROLD MOSER