| Plan Review Notes For Permit 11030363 |
| Permit Number |
11030363 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-17 09:02:19 | PLANS DENIED | | | | | | 1. VENITLATION REQUIRED IN STEAM ROOM AND SHOWER, FBC M | | | 403. VENTILATION NOT SPECIFIED IN THE SHOWER AND NOT | | | SPECIFIED OR SHOWN IN THE STEAM ROOM. | | | | | | 2. VENTILATION NOT SHOWN OR SPECIFIED IN THE W/C ROOMS, | | | FBC M 403. | | | | | | 3. PLEASE REVIEW PLAN TO PROVIDE MORE INFORMATION | | | REGARDING W/C ROOMS, A SMALL SYMBOL FOR SUPPLY IS SHOWN | | | IN ONE BUT NOT IN THE NEW ALTERED W/C. PLEASE SHOW ALL | | | EXISTING AND PROPOSED NEW SUPPLY FBC M 403. | | | | | | 4. ELECTRIC PLAN SHOWS TWO WATER HEATERS, SHEET M2 | | | SHOWS ONE. PLEASE CORRELATE. ARE THEY GAS OR ELECTRIC | | | WATER HEATERS? FBC M 1002. | | | | | | PLAN REVIEW BY HAROLD MOSER |
|