| Plan Review Notes For Permit 11030363 |
| Permit Number |
11030363 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-24 14:46:13 | 2260 PALM BEACH LAKES BOULEVARD, SUITE #215 | | | PERMIT #11030363 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS ON THE COVER SHEET AND THE ADDRESS IN THE | | | TITLEBLOCK DO NOT MATCH. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE | | | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE | | | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA | | | EDITION 2007. | | | | | | IDENTIFY POINT OF COMPASS ON FLOOR PLANS. | | | | | | PROVIDE A ONE HOUR FIRE RATED TENANT SEPARATION WITH | | | ADJACENT TENANT SPACE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|