Plan Review Notes
Plan Review Notes For Permit 11030363
Permit Number 11030363
Review Stop E
Sequence Number 1
Notes
Date Text
2011-03-14 14:18:361. GFCI PROTECTION IS REQUIRED FOR GENERAL PURPOSE
 RECEPTACLES LOCATED IN THE LUNCH ROOM. NEC 210.8(B)
 2. SHOW THE LOCATION OF THE PANELBOARD. NEC 110.26,
 408.18
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  