2011-03-16 16:03:51****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE DESIGN OCCUPANT LOAD FBC1004.1.
  
 2. INCLUDE THE FOLLOWING IN THE PROJECT INFORMATION:
 BUILDING TYPE, FBC CHAPTER
 SPRINKLERED OR NON SPRINKLERED BUILDING
  
 3. REVISE PLAN TO SHOW DISTANCE BETWEEN MASSAGE ROOM 5
 AND THE PROPOSED PARTITION (WHICH APPEARS TO BE A CHECK
 OUT COUNTER), FBC1014.4.1.
  
 4. IT APPEARS THAT AN EXTERIOR DOOR IS TO BE REPLACED
 WITH STOREFRONT. SPECIFY DESIGN PRESSURES FBC 1609 AND
 PROVIDE PRODUCT APPROVAL FOR THE STOREFRONT AND
 MULLIONS IF APPLICABLE.
  
 5. A BENCH IS SHOWN IN FRONT OF THE STOREFRONT. IS THE
 STOREFRONT FULL HEIGHT AS IT IS REPLACING A DOOR, WITH
 THE BENCH BLOCKING THE WINDOW, OR WILL THERE BE WALL
 INFILL? PROVIDE A DETAIL FBC1609.
  
 6. PROVIDE A DETAIL FOR THE STEAM ROOM AND SHOWER WALLS
 FBC2509. INCLUDE INSULATION FBC 13 101.4.1.1.
  
 7. SPECIFY DOOR TYPE FOR THE STEAM ROOM, FBC 13
 101.4.1.1.
  
 8. REVISE PLAN TO DESIGNATE W/C USE (SUCH AS UNISEX,
 PRIVATE, MENS, WOMENS, ETC.) FBC 11. ONE W/C IS BEING
 ALTERED BUT DOES NOT PROVIDE TURNING RADIUS. SEE FBC
 11-4.1.6(2).
  
 9. SHOW PULL SIDE CLEARANCE (MINIMUM 18INCHES) FOR
 RECEPTION INTERIOR DOOR, FBC FIGURE 11 25.
  
 10. THE STEAM ROOM DOOR OBSTRUCTS EXITING FROM THE
 SHOWER, FBC 1005.2 AND EGRESS THROUGH THE STEAM ROOM
 DOOR IS NOT ORIENTED TOWARDS THE EXIT.
  
 11. MECHANICAL VENTILATION IS REQUIRED IN THE STEAM
 ROOM FBC 1203.4.2.1.
  
 12. PROVIDE A DETAIL FOR WALL FRAMING FBC 106, FBC 6.
  
 13. PROVIDE INFORMATION REGARDING ACCESSIBLE ELEMENTS
 FBC 11-4.1.6(2).
  
  
  