| 2011-03-16 16:03:51 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PROVIDE DESIGN OCCUPANT LOAD FBC1004.1. |
| | |
| | 2. INCLUDE THE FOLLOWING IN THE PROJECT INFORMATION: |
| | BUILDING TYPE, FBC CHAPTER |
| | SPRINKLERED OR NON SPRINKLERED BUILDING |
| | |
| | 3. REVISE PLAN TO SHOW DISTANCE BETWEEN MASSAGE ROOM 5 |
| | AND THE PROPOSED PARTITION (WHICH APPEARS TO BE A CHECK |
| | OUT COUNTER), FBC1014.4.1. |
| | |
| | 4. IT APPEARS THAT AN EXTERIOR DOOR IS TO BE REPLACED |
| | WITH STOREFRONT. SPECIFY DESIGN PRESSURES FBC 1609 AND |
| | PROVIDE PRODUCT APPROVAL FOR THE STOREFRONT AND |
| | MULLIONS IF APPLICABLE. |
| | |
| | 5. A BENCH IS SHOWN IN FRONT OF THE STOREFRONT. IS THE |
| | STOREFRONT FULL HEIGHT AS IT IS REPLACING A DOOR, WITH |
| | THE BENCH BLOCKING THE WINDOW, OR WILL THERE BE WALL |
| | INFILL? PROVIDE A DETAIL FBC1609. |
| | |
| | 6. PROVIDE A DETAIL FOR THE STEAM ROOM AND SHOWER WALLS |
| | FBC2509. INCLUDE INSULATION FBC 13 101.4.1.1. |
| | |
| | 7. SPECIFY DOOR TYPE FOR THE STEAM ROOM, FBC 13 |
| | 101.4.1.1. |
| | |
| | 8. REVISE PLAN TO DESIGNATE W/C USE (SUCH AS UNISEX, |
| | PRIVATE, MENS, WOMENS, ETC.) FBC 11. ONE W/C IS BEING |
| | ALTERED BUT DOES NOT PROVIDE TURNING RADIUS. SEE FBC |
| | 11-4.1.6(2). |
| | |
| | 9. SHOW PULL SIDE CLEARANCE (MINIMUM 18INCHES) FOR |
| | RECEPTION INTERIOR DOOR, FBC FIGURE 11 25. |
| | |
| | 10. THE STEAM ROOM DOOR OBSTRUCTS EXITING FROM THE |
| | SHOWER, FBC 1005.2 AND EGRESS THROUGH THE STEAM ROOM |
| | DOOR IS NOT ORIENTED TOWARDS THE EXIT. |
| | |
| | 11. MECHANICAL VENTILATION IS REQUIRED IN THE STEAM |
| | ROOM FBC 1203.4.2.1. |
| | |
| | 12. PROVIDE A DETAIL FOR WALL FRAMING FBC 106, FBC 6. |
| | |
| | 13. PROVIDE INFORMATION REGARDING ACCESSIBLE ELEMENTS |
| | FBC 11-4.1.6(2). |
| | |
| | |
| | |