Plan Review Notes
Plan Review Notes For Permit 11030351
Permit Number 11030351
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-04-07 17:10:46464 FERN STREET
 PERMIT #11030351
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 THE FIXED DOOR LEAF OF THE EAST EXIT SHALL BE BE MADE
 VISIBLY OBVIOUS THAT THE DOOR LEAF IS INOPERABLE AS AN
 EXIT.
  
 POST BUILDING ADDRESS ON SIDE OF BUILDING FACING FERN
 STREET. NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT
 AND SHALL CONTRAST WITH THE BACKGROUND COLOR.
  
 BUILDING SHALL BE LABELED WITH A REFLECTIVE
 WEATHERPROOF MALTESE CROSS INDICATING THE BUILDING IS
 CONSTRUCTED OF LIGHTWEIGHT FRAMING CONSTRUCTION FOR THE
 FLOOR AND ROOF ASSEMBLIES PER FLORIDA STATUTE 633.027.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE 18 INCH DEEP NONCOMBUSTIBLE DRAFTSTOPS FOR NEW
 SPRINKLER WATER CURTAIN. DRAFTSTOPS SHALL BE LOCATED ON
 THE FIRST FLOOR CEILING IMEDIATELY ADJACENT TO THE TWO
 UNENCLOSED VERTICAL OPENINGS PER NFPA 13 SECTION
 8.14.4.
  
 PROVIDE EXIT SIGNAGE ON SECOND FLOOR DIRECTING
 OCCUPANTS TO THE EXTERIOR STAIR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  