| 2011-03-18 10:30:16 | 2ND REVIEW. |
| | |
| | THE ELECTRICAL PLANS ARE INCOMPLETE. |
| | |
| | INDICATE THE PROPOSED WIRING METHODS. THE PLANS SHOULD |
| | INCLUDE THE ELECTRICAL RISER, PANEL SCHEDULE, PANEL |
| | LOCATION, BRANCH CIRCUIT SIZES, SERVICE SIZE, SERVICE |
| | LOCATION, SERVICE RATING, ELECTRICAL LOAD CALCULATION |
| | AND FAULT CURRENT CALCULATION. THE EXISTING WIRING |
| | METHOD MUST COMPLY WITH THE OCCUPANCY TYPE. NEC 110.3 |
| | |
| | PATIENT CARE AREAS AND EXAMINING ROOMS, # 103, 104, |
| | 113, 112, 111 AND 114 SHALL PROVIDE AN EFFECTIVE |
| | GROUND-FAULT RETURN PATH USING METAL RACEWAYS, METALLIC |
| | CABLE ARMOR ASSEMBLY QUALIFIED AND LISTED AS AN |
| | EQUIPMENT GROUNDING METHOD. RECEPTACLES WITHIN THESE |
| | ROOMS ARE REQUIRED TO HAVE AN INSULATED GROUNDING |
| | TERMINAL. NEC 517.13 (A), (B), NEC 517.167 |
| | |
| | PROVIDE THE ELECTRICAL SPECIFICATIONS, FEEDER SIZE, |
| | OVERCURRENT SIZE AND LISTING FOR THE X-RAY MACHINE. NEC |
| | 110.3, 517.71 |
| | PROVIDE THE RATING AND LOCATION OF THE X-RAY |
| | DISCONNECTING MEANS. NEC 517.72 |
| | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE |
| | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES |
| | IN ACCORDANCE WITH THE FLORIDA ENERGY CODE |
| | REQUIREMENTS. FBC 13-415 ABC.1.2. |
| | |
| | THE SECOND FLOOR ELECTRICAL LAYOUT WAS NOT PROVIDED |
| | |
| | |