Plan Review Notes
Plan Review Notes For Permit 11030351
Permit Number 11030351
Review Stop E
Sequence Number 2
Notes
Date Text
2011-03-18 10:30:162ND REVIEW.
  
 THE ELECTRICAL PLANS ARE INCOMPLETE.
  
 INDICATE THE PROPOSED WIRING METHODS. THE PLANS SHOULD
 INCLUDE THE ELECTRICAL RISER, PANEL SCHEDULE, PANEL
 LOCATION, BRANCH CIRCUIT SIZES, SERVICE SIZE, SERVICE
 LOCATION, SERVICE RATING, ELECTRICAL LOAD CALCULATION
 AND FAULT CURRENT CALCULATION. THE EXISTING WIRING
 METHOD MUST COMPLY WITH THE OCCUPANCY TYPE. NEC 110.3
  
 PATIENT CARE AREAS AND EXAMINING ROOMS, # 103, 104,
 113, 112, 111 AND 114 SHALL PROVIDE AN EFFECTIVE
 GROUND-FAULT RETURN PATH USING METAL RACEWAYS, METALLIC
 CABLE ARMOR ASSEMBLY QUALIFIED AND LISTED AS AN
 EQUIPMENT GROUNDING METHOD. RECEPTACLES WITHIN THESE
 ROOMS ARE REQUIRED TO HAVE AN INSULATED GROUNDING
 TERMINAL. NEC 517.13 (A), (B), NEC 517.167
  
 PROVIDE THE ELECTRICAL SPECIFICATIONS, FEEDER SIZE,
 OVERCURRENT SIZE AND LISTING FOR THE X-RAY MACHINE. NEC
 110.3, 517.71
 PROVIDE THE RATING AND LOCATION OF THE X-RAY
 DISCONNECTING MEANS. NEC 517.72
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 IN ACCORDANCE WITH THE FLORIDA ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.1.2.
  
 THE SECOND FLOOR ELECTRICAL LAYOUT WAS NOT PROVIDED
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  
  
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  