Plan Review Notes
Plan Review Notes For Permit 11030351
Permit Number 11030351
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-03-18 17:08:05464 FERN STREET
 PERMIT #11030351
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 241.
  
 NEW WORK SHALL COMPLY WITH THE LIFE SAFETY REQUIREMENTS
 OF THE FLORIDA FIRE PREVENTION CODE 2007 EDITION.
  
 SHEET G101 TITLED LIFE SAFETY PLAN WAS NOT PROVIDED.
  
 CLASSIFICATION OF OCCUPANCY NOT PROVIDED.
  
 NO INFORMATION ON EGRESS PROVIDED, SUCH AS STAIR
 HANDRAILS, STAIR GUARDRAILS, SLOPE OF RAMP, DOOR
 LOCKS/LATCHES, SLIP RESISTANCE ETC.
  
 EXISTING FIRE SPRINKLER SYSTEM OR FIRE ALARM SYSTEM
 INFORMATION NOT PROVIDED.
  
 INFORMATION FOR THE SECOND LEVEL FLOOR PLAN NOT
 PROVIDED.
  
 POST BUILDING ADDRESS ON SIDE OF BUILDING FACING FERN
 STREET. NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT
 AND SHALL CONTRAST WITH THE BACKGROUND COLOR.
  
 BUILDING SHALL BE LABELED WITH A REFLECTIVE
 WEATHERPROOF MALTESE CROSS INDICATING THE BUILDING IS
 CONSTRUCTED OF LIGHTWEIGHT FRAMING CONSTRUCTION FOR THE
 FLOOR AND ROOF ASSEMBLIES PER FLORIDA STATUTE 633.027.
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR MODIFICATIONS
 TO FIRE SPRINKLER OR FIRE ALARM SYSTEMS.
  
 A THOROUGH REVIEW OF THE DRAWINGS CANNOT BE COMPLETED
 UNTIL A COMPLETE PLAN SET HAS BEEN PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW