2011-03-14 13:00:16BUILDING PLAN REVIEW
 PERMIT: 11030351
 ADD: 464 FERN ST
 CONT: TO BE DETERMINED
 TEL: (561)644-7416
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATOR???S
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIROMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIROMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
  
  
  
  
  
 1) THIS BUILDING APPEARS TO BE A CONVERSION FROM A R-3
 RESIDENCE TO AN OFFICE USE OCCUPANCY OR A CHANGE OF
 OCCUPANCY THAT TRIGGERS THE USE OF CHAPTER 9 OF
 THE2007/ 2009 FBC- EXISTING BUILDING CODE. NO RECORDS
 WERE FOUND IN THE COMPUTER BASE INDICATING A CHANGE IN
 USE PERMIT.
  
 2) 2007 EXST BLDG CODE 906.1 ACCESSIBILITY IN PORTIONS
 OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING . 912.8 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
  
 11-4.1.6 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH
 OF TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
 (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
 (IV) ACCESSIBLE TELEPHONES;
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
 PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE FROM THE PUBLIC WAY. 11-4.1.6(1)(B) .
  
 3) THIS BUILDING IS INDICATED AS A TWO STORY BUILDING
 BY THE COVER SHEET AND INTERNAL WINDER STAIR. THE PLANS
 DO NOT INDICATE ANY 2ND FLOOR INFORMATION,
 11-4.1.6(1)(III) VERTICAL ACCESSIBILITY.
  
 4) 2007/ 2009 EXST BLDG CODE 907.1 GRAVITY LOADS.
 BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED
 ON THE FLORIDA BUILDING CODE, BUILDING TABLE 1607.1
 SHALL COMPLY WITH THE GRAVITY LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 AS A R-3 RESIDENCE THE FLOOR LOAD DESIGN WOULD HAVE
 BEEN 30 PSF FOR SLEEPING AREAS AND 40 PSF FOR OTHER
 HABITABLE AREAS, FOR A BUSINESS OCCUPANCY 50 PSF WILL
 BE THE DESIGN LOAD.
 A GREATER LOAD THAN THE EXCEPTION: STRUCTURAL ELEMENTS
 WHOSE STRESS IS NOT INCREASED BY MORE THAN 5 PER CENT
 WOULD MEET THE EXCEPTION. PLEASE INDICATE COMPLIANCE
 WITH THIS SECTION, ALSO NOTE IN ROOM # 104 THE X-RAY
 EQUIPMENT AND EXTREMELY HEAVIER LOADS.
 SHEET A-102 DETAIL # 1 APPEARS TO TRY TO MEET CODE
 COMPLIANCE FOR GRAVITY LOADS BUT NO
 LIVE LOAD DESIGNS WERE PROVIDED.
  
 5) 435.5.1 SHIELDING. EACH X-RAY FACILITY SHALL HAVE
 PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO
 ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION
 DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF
 CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE . CONTACT:
 TOM TOMCZAK (904) 278-5730
 705 ROSE RD SUITE# 300
 ORANGE PARK, FL 32073
  
 6) BOTH G-101 AND A-101 INDICATE A SLOPED RAMP IN THE
 INTERIOR OF THE BUILDING BUT NO INFORMATION WAS
 PROVIDED.
 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE SHALL
 BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM RISE FOR
 RUN SHALL BE 30" (SEE FIGURE 16).
 11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH OF A
 RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  