| 2011-04-11 12:54:06 | BUILDING PLAN REVIEW |
| | PERMIT: 11030300 |
| | ADD: 2201 45TH ST- MAIN HOSPITAL |
| | CONT: M. J. HARRIS, INC |
| | TEL: (615)499-0183 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A2.01D NEW WORK ITEM # 74 DRESSING ROOM |
| | PLANS ARE UNCLEAR AS TO THE USAGE OF THE DRESSING ROOM, |
| | IS IT FOR PATIENTS OR FOR WORKERS WITHIN THE HOSPITAL? |
| | PLEASE IDENTIFY IF THIS DRESSING ROOM IS TO BE FOR |
| | PATIENTS OR FOR HOSPITAL PERSONAL. |
| | |
| | 11-4.1.1(3) AREAS USED ONLY BY EMPLOYEES AS WORK AREAS. |
| | AREAS THAT ARE USED ONLY AS WORK AREAS SHALL BE |
| | DESIGNED AND CONSTRUCTED SO THAT INDIVIDUALS WITH |
| | DISABILITIES CAN APPROACH, ENTER, AND EXIT THE AREAS. |
| | THIS CODE DOES NOT REQUIRE THAT ANY AREAS USED ONLY AS |
| | WORK AREAS BE CONSTRUCTED TO PERMIT MANEUVERING WITHIN |
| | THE WORK AREA OR BE CONSTRUCTED OR EQUIPPED (I.E., WITH |
| | RACKS OR SHELVES) TO BE ACCESSIBLE. |
| | |
| | 1A) DOOR LOCATION (H) BY WALL BEING CUT BACK AND |
| | LEAVING A 6 INCH PROJECTION.THE DOOR DOES NOT HAVE 18 |
| | INCHES CLEARENCE ON THE LATCH SIDE OF THE DOOR. |
| | 11-4.13.6. PLEASE ALSO REVIEW A4.02 DOOR TYPE (H) IS |
| | LABELED EITHER A SLIDING OR FOLDING DOOR. |
| | |
| | 1B) IF THE DRESSING ROOM IN QUESTION IS TO BE FOR |
| | PATIENT USE THEN THE REQUIREMENTS FOR DRESSING ROOMS |
| | WILL NEED TO BE REVIEWED 11-4.35 (1-5). |
| | |
| | 1C) THE PLANS DO NOT INDICATE ANY WORK TO BE COMPLETED |
| | WITHIN THE LOCKER AREA IF THE LOCKERS ARE TO BE FOR |
| | PATIENT USAGE THEN REACH RANGES MAY BE A CONCERN, |
| | REVIEW 11-4.2.5 FOR FORWARD REACH AND 11-4.2.6 FOR SIDE |
| | REACH. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |