| Plan Review Notes For Permit 11030288 |
| Permit Number |
11030288 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-06-08 12:02:01 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE PRODUCT APPROVALS FOR PRECAST LINTELS. NEED | | | ONE FOR 8" LINTELS. | | | | | | 2- ENGINEER TO PROVIDE WINDOW 2X STRUCTURAL BUCK DETAIL | | | ATTACHMENT TO SUBSTRATE AS REQUIRED BY THE PRODUCT | | | APPROVALS SUBMITTED. | | | | | | 3- NEED TO PROVIDE 36" MIN. STAIR LANDING AT BOTTOM OF | | | STAIRS. SEC. R311.5.4. | | | | | | 4- SECOND FLOOR FRAMING PLAN: REVISE THE LIVE LOADS. | | | REVISE LIVE LOAD FOR OTHER ROOMS OTHER THAN SLEEPING | | | ROOMS. SEE TABLE R301.5. | | | | | | B) PROVIDE SECTION/DETAIL AND SPECIFICATIONS SHOWING | | | HOW THE EXISTING ROOF TRUSSES ARE GOING TO BE CUT TO BE | | | BEARING ON THE 2 STORY WALL LEDGER. SHOW HOW ARE THE | | | CUT TRUSSES REINFORCED TO PROVIDE LOAD TRANSFER | | | CONTINUITY AT THE CUT SECTION. |
|