2011-03-31 10:29:25RESIDENTIAL (R3) ADDITION PLUMBING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE W/ 2009 REVISIONS.
  
 1- PROVIDE PLUMBING RISER DIAGRAM THAT MATCHES FLOOR
 PLANS. PLANS DON'T SHOW WASHER. KITCHEN SINK IS DOUBLE.
 DRAINAGE SHOWN ON THE SECOND FLOOR FOR THE TUB IS NOT
 CLEAR. REVISE AS REQUIRED.
  
 2- ENGINEER SHOWN ON THE TITLE BLOCK TO SIGN AND SEAL
 DRAWING AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN AND SIGNED
 BY THE PLUMBING CONTRACTOR.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6712.