| 2011-03-31 10:26:06 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SPECIFICATIONS ON PLANS. | | | | | | 2- ENGINEER SHOWN ON THE TITLE BLOCK TO SIGN AND SEAL | | | THE MECHANICAL SHEETS AS REQUIRED BY CHAPTER 471 | | | FLORIDA STATUTES. | | | **NOTE: PLANS MAY BE DRAWN AND SIGNED BY THE MECHANICAL | | | CONTRACTOR. | | | | | | 3- CONDENSING UNIT MOUNTING DETAIL: CLARIFY NUMBER OF | | | STEEL ANGLES REQUIRED. ARE THEY 2 ON EACH SIDE OR ONLY | | | ONE ON EACH SIDE? | | | | | | 4- ARE THERE 3 A/C UNITS OR 2?. PLANS SHOW USING ONLY 2 | | | AIR HANDLER UNITS. WHAT HAPPENS TO THE EXISTING AIR | | | HANDLER UNIT IN THE GARAGE? | | | | | | 5- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS THAT MATCH | | | A/C PLANS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|