| Plan Review Notes For Permit 11030281 |
| Permit Number |
11030281 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-23 13:40:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE | | | PROPOSED WORK, INCLUDING SIZE OF THE AWNING. | | | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. | | | | | | 3. PLEASE ADVISE, HOW HAS THE STRUCTURAL INTEGRITY OF | | | THE EXISTING AWNING BEEN DETERMINED? I WAS UNABLE TO | | | LOCATE A PERMIT FOR THE AWNING. OUR COMPUTERIZED SYSTEM | | | HAS RECORDS FROM 1998 TO PRESENT. IF THE AWNING WAS | | | INSTALLED WITHOUT A PERMIT, PROVIDE ENGINEERING. IF IT | | | WAS INSTALLED WITH A PERMIT PRIOR TO 1998, PROVIDE MORE | | | INFORMATION. | | | | | | 4. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | | BE NOTARIZED. | | | | | | |
|