| Plan Review Notes For Permit 11030257 |
| Permit Number |
11030257 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-17 16:06:34 | DENIED BY BUILDING | | | | | | 1) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS | | | OF +35.3 AND -47.2 PSF ARE TOO LOW FOR EXPOSURE C. | | | PLEASE CORRECT. | | | | | | 2) THE ENERGY FORM THAT WAS SUBMITTED IS NO LONGER | | | ACCEPTABLE. IT WAS CHANGED BY THE 2009 REVISIONS TO THE | | | ENERGY CODE. THE NEW FORM IS 1100B-08 | | | | | | 3) THE MINIMUM WALL INSULATION FOR A 2 X 6 WALL IS | | | REQUIRED TO BE R-13 PER THE PRESCRIPTIVE METHOD AND | | | ENERGY FORM 1100B-08. | | | | | | 4) ITEM # 4 ON SHEET 1 SHOULD REFERENCE THE 2008 NEC | | | AND NOT THE 2005 EDITION. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|