2011-03-17 16:06:34DENIED BY BUILDING
  
 1) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOWS
 OF +35.3 AND -47.2 PSF ARE TOO LOW FOR EXPOSURE C.
 PLEASE CORRECT.
  
 2) THE ENERGY FORM THAT WAS SUBMITTED IS NO LONGER
 ACCEPTABLE. IT WAS CHANGED BY THE 2009 REVISIONS TO THE
 ENERGY CODE. THE NEW FORM IS 1100B-08
  
 3) THE MINIMUM WALL INSULATION FOR A 2 X 6 WALL IS
 REQUIRED TO BE R-13 PER THE PRESCRIPTIVE METHOD AND
 ENERGY FORM 1100B-08.
  
 4) ITEM # 4 ON SHEET 1 SHOULD REFERENCE THE 2008 NEC
 AND NOT THE 2005 EDITION. PLEASE CORRECT.
  