| Plan Review Notes For Permit 11030186 |
| Permit Number |
11030186 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-08 09:00:17 | ****CORRECTIONS**** | | | ****REVISED 3/31**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. DESIGN PRESSURES CANNOT BE DETERMINED BASED ON | | | INFORMATION PROVIDED, FBC1609. PROVIDE BUILDING HEIGHT | | | AND A FLOOR PLAN SHOWING LOCATION OF PROPOSED DOOR. | | | | | | 2. THE FLOOR PLAN SHOWS A 90 MINUTE FIRE RATED DOOR | | | PROPOSED. | | | | | | IT APPEARS THAT A RATED DOOR IS NOT REQUIRED FOR THIS | | | LOCATION. IF THIS IS THE CASE, PLEASE REMOVE THIS | | | REQUIREMENT FROM THE FLOOR PLAN (IF APPLICABLE) AND | | | APPLICATION DESCRIPTION. IF A FIRE RATED DOOR IS | | | REQUIRED, PLEASE PROVIDE MORE INFORMATION REGARDING | | | DOOR INCLUDING LOCATION CONDITIONS WHICH WOULD REQUIRE | | | FIRE RATING (CORRIDOR, EXIT, ETC.), FIRE RATING | | | REQUIREMENT, AND DOOR HARDWARE INFORMATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER | | | ASSISTANCE. | | | | | | | | | |
|