| Plan Review Notes For Permit 11030180 |
| Permit Number |
11030180 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-03-23 16:32:26 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. ON THE DOOR PRODUCT APPROVAL, MARK THE OPTION | | | PROPOSED. PLEASE NOTE THAT MOST OF THE OPTIONS DO NOT | | | COMPLY WITH THE POSITIVE DESIGN PRESSURE REQUIREMENT. | | | | | | 2. ON THE SHUTTER INSTALLATION SCHEDULE, PLEASE REVISE | | | THE FOLLOWING: | | | | | | SHUTTER CONNECTION MOUNTING TYPE, THIS SHOULD CORRELATE | | | WITH THE ANCHOR CHARTS ON PAGES 10-11 (FOR INSTANCE, | | | WALL MOUNT 3 W/1" BO HEADER, OR FLOOR MOUNT 6, ETC.). | | | PLEASE NOTE THAT YOU HAVE SPECIFIED THE SUBSTRATE AS | | | CONCRETE BLOCK, BUT SOME REQUIRE A CONCRETE SUBSTRATE. | | | | | | 1 1/2" EDGE DISTANCE PROPOSED, SEE NOTE ON PAGE 11 OF | | | THE PRODUCT APPROVAL. EDGE DISTANCE LESS THAN 3 1/2" | | | REQUIRES A FACTOR TO BE APPLIED TO THE ANCHOR SPACING | | | IN THE CHARTS. | | | | | | NOTE THAT 12" SPACING FOR FLOOR MOUNT DOES NOT COMPLY | | | FOR THIS DESIGN PRESSURE, EVEN WITH 3 1/2" EDGE | | | DISTANCE. | | | | | | |
|